Étude d'un disjoncteur rapide pour courants intenses

A. Delmas, C. Rioux et F. Rioux-Damidau

Groupe Electrotechnique et Fusion Contrôlée, Laboratoire de Physique des Plasmas, Bât. 214, 91405 Orsay, France


Abstract
The circuit breaker presented here is capable of interrupting a 10 kA current within 1 μs and then sustain an over voltage of the order of 20 kV for a 3 mm insulation width. The construction is of the mechanical rupture type in which the replacement of a piece of conductor by an insulator is ensured by means of the explosion of a stoichiometric mixture of hydrogen and oxygen. The current is then transfered into a fuse which finally transfers the energy to the load or opens the circuit.


Résumé
Le disjoncteur présenté dans cet article est capable de couper un courant de 10 kA en 1 μs et de supporter une surtension de l'ordre de 20 kV pour une distance d'isolement de 3 mm. Ce disjoncteur est du type à rupture mécanique : le remplacement brutal d'un morceau de conducteur par un isolant est assuré par la surpression engendrée par l'explosion d'un mélange stoechiométrique d'hydrogène et d'oxygène. Le courant est alors dérivé sur une impédance variable (fusible) qui assure, soit le transfert d'énergie sur la charge, soit l'ouverture du circuit.